Experimental validation of cooling coil control valve performance with cascade control

Rodney Hurt, Gang Wang, Li Song

Research output: Chapter in Book/Report/Conference proceedingConference contribution

Abstract

Heating, Ventilation, and Air Conditioning (HVAC) systems operate at dynamic loads and may present unpredictable disturbances. Relatively minor disturbances can greatly affect the performance of certain subsystems, such as the cooling coil control valve. The operating error of the cooling coil control valve has the potential to compound with error from other subsystems and deteriorate the performance of the air handling unit (AHU). In many cases, the control systems are nonlinear and of high order, which reduces the likelihood of system stability with conventional control approaches. The objective of this paper is to experimentally evaluate the cooling coil control valve performance of cascade control by comparing it with a conventional Proportional-Integral (PI) control, on a nonlinear cooling coil control system. In the paper, the performances of both controls were compared first using a step change in reference input, i.e. supply air temperature setpoint step change and a step change in disturbance input, such as chilled water loop differential pressure (DP) step change. The primary testing criterion is the operating error, in terms of mean integral square error (mISE). System stability, settling time, and disturbance rejection are also considered in the comparison of the two control approaches. As a result, the cascade control is found to be the most effective when the valve system experiences pressure interruptions. For example, a maximum error of 0.46 °F for the cascade control and 0.95 °F for the single loop control were observed when the DP is reduced by 5 psi (27.8% of the operation value), while the mISE in the cascade control was only 5.5% of the single loop mISE. In addition, the mISE value of the cascade control is approximately 42% of the single loop mISE value for reference step change test.

Original languageEnglish (US)
Title of host publication2020 ASHRAE Virtual Conference
PublisherASHRAE
Pages233-241
Number of pages9
ISBN (Electronic)9781947192621
StatePublished - 2020
Externally publishedYes
Event2020 ASHRAE Virtual Conference - Virtual, Online
Duration: Jun 29 2020Jul 2 2020

Publication series

NameASHRAE Transactions
Volume126
ISSN (Print)0001-2505

Conference

Conference2020 ASHRAE Virtual Conference
CityVirtual, Online
Period6/29/207/2/20

ASJC Scopus subject areas

  • Building and Construction
  • Mechanical Engineering

Fingerprint

Dive into the research topics of 'Experimental validation of cooling coil control valve performance with cascade control'. Together they form a unique fingerprint.

Cite this